Overview:

• Classification Series :Indoor Vacuum Circuit Breaker

• Product Name :ZN23-40.5 Indoor vacuum circuit breaker

• Product Overview
Inlet/outlet of 12kV distribution system, distribution room of industrial and mining enterprises, box-type substation (adapted to XGN15-12, KYN28A-12 and other switchgear)...


Service
ZN23-40.5 Indoor vacuum circuit breaker
Product Introduction

▸ Product Introduction

Model meaning

Z: vacuum arc extinguishing

N: indoor installation

23: Design serial number

12: Rated voltage (kV)


Functional localization

Full current interruption: reliably interrupt rated current, overload current and short circuit current (up to 31.5kA).

Fast protection: the opening time is less than ≤50ms, and the fault cutting speed is better than the traditional model.


Typical application

Inlet/outlet of 12kV distribution system, distribution room of industrial and mining enterprises, box-type substation (adapted to XGN15-12, KYN28A-12 and other switchgear).


Operation accessory configuration

Operating power supply: DC 110V/220V or AC 220V V.

Auxiliary contact: 6 normally open+6 normally closed (including energy storage/on/off indication)


Locking function

It is forbidden to push/pull the handcart in the closing state.

The earthing switch is mechanically interlocked with the circuit breaker.


Type selection verification formula

Thermal stability check: I infty} 2 CDOTT LEQ I _ {th} 2 CDOT4I ∞ 2t ≤ ITH24 (fault thermal effect ≤ circuit breaker tolerance).

Altitude correction: when it is more than 1000m, the capacity will be reduced by 1% per 100m rated current.

Ambient temperature: -30℃-+40℃ (special design is required if it exceeds the range).


Critical threshold

Break-brake speed is 1.1 0.1 m/s (if the speed drops by more than 15%, it needs maintenance).

Contact overtravel is 3 0.5 mm (< 2.5 mm, the arcing chamber must be replaced).


Periodic maintenance

3 years /5000 operations:

Main circuit resistance measurement (standard: ≤ 40μ ω @ 1250a)

Mechanism lubrication (special low temperature grease)


Forced replacement of arc extinguishing chamber

Cumulative breaking short-circuit current reaches 300% Isc (for example, 25kA cumulative breaking 75kA).

Used for 10 years (even if the parameters are normal)


Iron law of safe operation

Five-proof interlock must be intact!

After breaking the brake, you must wait for ≥15s before operating the handcart (to ensure that the arc is completely extinguished).


Contact Information
  • Tel.:Manager Zheng:15319942044
  • Tel.:Manager Jin:18291881166
  • Email:service2@hwtmtrade.cn
    service1@hwtmtrade.cn
  • Location:Building 4, Enterprise No.1 Community, Yinshi Military Civilian Integration Industrial Park, No. 333 Yingbin Road, National Aviation High tech Industrial Base, Xi'an City, Shaanxi Province
Scan to follow the official official account Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.
15319942044 18291881166
Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.