Products
Current Location: Home > Products

Name:VEB-12 Indoor high voltage vacuum circuit breaker

Overview:

• Classification Series :Indoor Vacuum Circuit Breaker

• Product Name :VEB-12 Indoor high voltage vacuum circuit breaker

• Product Overview
Inlet/outlet protection of 12kV distribution system, core distribution station of industrial and mining enterprises, and high-voltage side of wind power/photovoltaic box transformer...


Service
VEB-12 Indoor high voltage vacuum circuit breaker
Product Introduction

▸ Product Introduction

Model decoding

V: Vacuum.

E: design serial number (Evolution)

B: Breaker.

12: Rated voltage level (kV)


Core function

Full-condition protection: interrupting rated current, overload current and maximum 50kA short-circuit current.

Fast isolation: the opening time is ≤35ms, and the fault cutting speed is 20% ahead of similar products.


Typical application

Inlet/outlet protection of 12kV distribution system, core distribution station of industrial and mining enterprises, and high-voltage side of wind power/photovoltaic box transformer (suitable for cabinets such as KYN28A-12 and XGN15-12).


Technical parameter

Parameter

Unit

Standard value range

Peak capacity

Rated voltage (Ur)

kV

12

-

Rated current (Ir)

A

630/1250/1600/2000/2500

3150 (customized)

Rated short-circuit breaking current (Isc)

kA

20/25/31.5/40

50  (enhanced)

Rated short-term withstand current (4s)

kA

= Isc

-

Rated peak withstand current

kA

50/63/80

100

Dielectric level




Power frequency withstand voltage (1min)

kV

42 (alternate)/ 48 (fracture)

-

Lightning impulse withstand voltage (peak value)

kV

75 (alternate)/ 85 (fracture)

-

Mechanical properties




Opening time

ms

≤35

-

Closing time

ms

≤75

-

On-off time

ms

≤60

-

Mechanical life

Frequency

≥30,000

-

Rated current electrical life

Frequency

≥10,000

-

Full capacity breaking times (Isc=40kA)

Frequency

≥50

-


Intelligent control accessory

Operating power supply: DC 48V/110V/220V or AC 220V.

Communication protocol: RS485+Modbus is standard and supports IEC 61850-8-1 (optional).

Protection interface: 4× passive contact (on/off/energy storage/fault)


Key technical requirements for operation and maintenance

Mechanical characteristics monitoring:

Warning value: brake opening speed decreases by > 15% or overtravel changes by > 2mm → trigger maintenance warning.


Periodic maintenance

3 years /5000 operations: measure the resistance of the main circuit (standard: ≤25μΩ @ 1250A).

10 years: replace vacuum interrupter (depending on wear monitoring data)


Safety interlock

Forced locking logic: it is forbidden to operate the grounding knife switch when the circuit breaker is closed (in line with GB 3906 Five Preventions).


Contact Information
  • Tel.:Manager Zheng:15319942044
  • Tel.:Manager Jin:18291881166
  • Email:service2@hwtmtrade.cn
    service1@hwtmtrade.cn
  • Location:Building 4, Enterprise No.1 Community, Yinshi Military Civilian Integration Industrial Park, No. 333 Yingbin Road, National Aviation High tech Industrial Base, Xi'an City, Shaanxi Province
Scan to follow the official official account Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.
15319942044 18291881166
Heweitongmao (Shaanxi) Import & Export Trade Co., Ltd.